HVP12 Intelligent
valve positioner is a necessary accessory for intelligent pneumatic actuator.
Its operating principle is completely different from analog positioner.HVP
Intelligent valve positioner and pneumatic actuator construct a feedback
control loop, in this return circuit, the valve position feedback signal is
regarded as a variablecomparing with given signal in microprocessor and the
D-value between them sends out different length of pulse through the outlet of
the main control panel to control the output pressure of the I/P conversion
unit, thereby the control valve is driven to act.HVP11 Intrinsically-safety
type,HVP12 Explosion-proof type.
FEATURES:
1. High accuracy
to class 0.5;
2. Set and select
output characteristics at will;
3. Low power and air
consumption, high vibration resistance and it is suitable for bad environment;
4. It can match up
with any actuators with different size automatically;
5. Remote
configuration and monitoring can be available with superior computer or hand
terminal end;
6. Self-diagnosis
function for signals outrange, input signal interruption and valve position
signal interruption.;
7. Failure mode:Full open, full close, holding and switch to hand
movement;
8.
Communication with HART
and PROFIBUS-PA protocol;
9. Current
feedback function: output 4~20mA valve position signal.
STANDARD SPECIFICATION
Series
|
HVP12
|
Model
|
HVP□□□□□□□□
|
Input signal
|
4~20mA analog signal or digit signal
|
Input resistance
|
450Ω
|
Air supply
|
0.2MPa~0.55MPa
|
Air consumption
|
≤0.6NL/min
|
Travel
|
10~100mm(Corner 60~90°)
|
Limit of intrinsic error
|
±0.5%,±1.0%(Standard)
|
Hysteresis error
|
≤0.5%
|
Dead band
|
≤0.1%(Min)
|
Conditions of
working atmosphere
|
a、Ambient temp.:-30~+80°C,
-40~+80°C(Low
temp.)
b、Ambient humidity:5%~95%
c、Ambient atmosphere:86~106k
d、There is no corrosive gas in ambient air
|
Display
|
LCD(Note: Displays is fuzzy
when the temp. is lower than-20°C)
|
Explosion-proof
level
|
Ex dIICT6(Intrinsically Safe,
Explosion-Proof Certification: Pass the test of explosion-proof and
intrinsically-safety by the qualification bodies with explosion-proof
certification,
|
Protection
grade
|
IP65
|
Electric
wiring connection
|
M20X1.5-7H(Standard)、1/2NPT、G1/2
|
Air
wiring connection
|
Rc1/4″、1/4NPT、G1/4
|
Shell
material
|
ADC12
|
Weight
|
3.0kg
|
Fig.1 EXTERNAL DIMENSIONS
Fig. 1-1 Overall dimensions of
HVP12
Fig.2 WIRING DIAPHRAGM
Fig.2-1
HVP12 Input signal connection
Allowable
load resistance RB<(U-18)/I
max RB=K, U=V, I max=Ma
Fig.2-2
HVP12 Current feedback connection
Model
|
订货号Order No.
|
Intelligent valve positioner
|
HVP
|
|
|
|
|
|
|
|
|
|
|
|
Piezoelectric explosion-proof
|
12
|
|
|
|
|
|
|
|
Single acting
|
1
|
Liner stem motion
Rotary stem motion
|
L
R
|
Without communication protocol
HART Protocol
|
0
1
|
Without auxiliary module
Current feedback module
|
0
1
|
Electric wiring connection 20x1.5-7H
1/2NPT
G1/2
|
0
1
2
|
Air wiring connection Rc1/4
1/4NPT
G1/4
|
0
1
2
|
Others
|
|
Thank you for your visit, if necessary,
welcome to contact us, we will do our best to provide services for you.
Contact:023-61067711;15123158485(微信) QQ:1831598138